Photo is of a completed ShadowFX static-dissipative (ESD) carpet installation in an electronics manufacturing and assembly facility.
  • What is ESD?

ESD stands for electrostatic discharge. The shock you feel when you slide across a car seat on a cold, dry day then touch the door handle is a common, usually harmless ESD event. In workplaces that manufacture, handle or use sensitive electronic devices, ESD is a destructive and invisible force.

ESD events can damage electronic parts during the manufacturing process. ESD can also affect the performance of operational electronic systems like communication equipment in 9-1-1 call centers, servers, data storage systems, and even navigation equipment in flight control operations. At the networked office level, ESD can cause communication errors, equipment freeze-ups and system crashes.

  • How is ESD measured and detected?

Most ESD events go unnoticed. Like the common cold, ESD is an invisible problem: there is rarely a spark associated with most ESD events in the workplace. We discover that electronic systems have been affected only after we notice the symptoms.

When investigating an ESD event, we start by performing a series of tests to determine whether the flooring and seating in the workspace can generate a static charge on a person sufficient to cause a discharge. To do this, we use an instrument called an electrostatic field meter. This instrument measures the accumulation of static on people and furniture.

Since people walking on floors cause most static problems, we usually measure the static charge on people while they’re sitting and as they move throughout the space. If we observe a quick accumulation of static, we know that the floor is a likely culprit.

Typical Electrostatic Voltages measured on a charged person at 20% Relative Humidity:

1. Sliding across a foam seat cushion
2. Walking across a vinyl floor
3. Walking across nylon carpet 
4. Walking across computer grade carpet  
5. Walking across StaticWorx static-dissipative carpet 

10-14 kV
8-12 kV
3-15 kV
<3.5 kV
<0.4 kV

1. Sliding across a foam seat cushion 10-14 kV
2. Walking across a vinyl floor 8-12 kV
3. Walking across nylon carpet 3-15 kV
4. Walking across computer grade carpet <3.5 kV
5. Walking across StaticWorx static-dissipative carpet <0.4 kV

  • How sensitive are electronic parts to ESD events?

Electronic parts – like the small assemblies inside disc drives – can be damaged by static discharges as low as 5 to 10 volts. Several hundred to a couple thousand volts of static can affect electronic systems.

To put the numbers in perspective, human beings cannot even feel a static discharge until the voltage levels reach 3500 volts (3.5 kV.) 

Illustration shows a hand with a finger reaching out to touch a doorknob.. The finger glows where it touches and numerous blue circles with minus signs in represent the elections being transferred or the static charge. The label above reads "At least 3500 volts" representing the human threshold of sensitivity to electrostatic discharge (ESD)

To protect electronic equipment from damage due to random static discharge, ESD-control floors like static-dissipative carpet should prevent static charges from exceeding 400 volts for end-user spaces (e.g. call centers and flight towers), 100 volts in electronics manufacturing and handling facilities (EPAs) and 10 volts in Class-0 environments.

  • How does ESD damage computers and cause downtime?

Static electricity builds on people as they walk or move around the enviroment and discharges to people or equipment they touch. When a charged person touches an electronic component, static jumps from the person to the equipment. Electronics perceive these electrostatic charges as electrical signals to perform unintended functions. ESD triggered signals are random and many are undiagnosed. 

A few real-life examples of ESD events are:

  • How does static charge generation affect a static-control carpet specification?

In critical operations, which must function continually without disruption, electronic parts cannot be exposed to static charges. Electrical resistance – a floor’s ability to promote or resist the flow of electricity – is unrelated to and has no effect on static charge generation. Depending upon the flooring material and type of shoes people wear in the space, a conductive or dissipative ESD floor can generate significant static charges.

To prevent static events, the ESD floor needs to be conductive or dissipative and antistatic – i.e, prevent static from accumulating on workers and visitors – and must be static-free regardless of the kinds of shoes people are wearing. 

Some ESD flooring products (some vinyl and epoxy materials in particular) are intended for use in combination with special ESD footwear and don’t have the ability to prevent static on ordinary street shoes. In fact, without the use of special ESD-protective footwear, because of their static-generating base materials, these floors can actually generate static on people as they walk. ESD carpet and rubber, on the other hand, can be manufactured with special static-dissipative ESD preventive properties that allow people to generate little to no static regardless of the type of shoes they are wearing. 

Architects need to understand how to write a specification that will ensure the correct floors are installed and certified for use.

A proper static control floor needs to eliminate static and needs to do it safely. Our article The Need for Due Diligence in Specifying ESD Flooring provides a good starting place for anyone tasked with specifying effective antistatic flooring solutions that also meet the professional standard of care through compliance with electrical safety standards for installation around operational electrical equipment.

  • Why is antistatic protection in conventional carpets insufficient for today's workplace?

Conventional anti-static carpet is designed to prevent static shocks. Because it has no inherent conductivity, it cannot be grounded and therefore cannot dissipate – or transport – static charges to ground. Humans can’t feel static shocks until the voltage exceeds 3 kV (3000 volts). A 1000 to 3500 volt discharge – common with conventional antistatic carpeting – could harm electronic equipment without anyone knowing it occurred.

ESD is an invisible problem requiring a preemptive approach. When people walk on carpet in a critical operational environment, the floor needs to dissipate static charges to ground. The floor must also prevent static generation in the first place.

StaticWorx ShadowFX static-dissipative (SD) carpet, designed to enhance the comfort of people in the space, improves the performance of electronic equipment by keeping static charges below .4 kV (400 volts).

Please note: Static electricity is generated from sources other than the carpeted floor, such as clothing, the interaction of clothing and seat fabrics, plastic, etc.

Conventional anti-static carpet ensures ONLY that the carpet itself does not generate harmful static charges – in other words, that people do not get a shock when they touch someone or something after walking on the floor.

Partial image of Dave holding an ohmmeter. At the bottom, the series title Static Shorts with StaticWorx displays along with the logo in a blue box. Below that in a gray blue box is the episode title in white 'Low kV is Not Static Free'
Play Video
Partial image of Dave holding an ohmmeter. At the bottom, the series title Static Shorts with StaticWorx displays along with the logo in a blue box. Below that in a gray blue box is the episode title in white 'Low kV is Not Static Free'
Play Video
  • What is conductivity?

We use a unit of measure called the Ohm to describe a material’s ability to conduct or resist the flow of electricity. Electrical Resistance or Resistive Properties are a material’s ability to transport an electrical charge to ground. Ground points can be an AC electrical outlet box, an I beam in the building infrastructure or a dedicated rod driven into the earth. Grounding a floor – also called earthing – requires connecting the antistatic floor to a point in an electrical circuit or building infrastructure that has zero electrical potential. An ESD Ground provides a path for the dissipation of unwanted static electricity charges.

Conductor is a material with low electrical resistance that rapidly removes an electrical charge to ground. Examples of conductors are water, copper, aluminum and carbon. Some ESD floors are conductive. These floors are usually used in special controlled areas for explosives handling or in ESD-protected areas in electronics manufacturing facilities.

Background image is a frame from the video showing insulator on one side and conductor on the other. In the foreground at the bottom are two boxes. The top is a bright blue with the StaticWorx logo. The second is a dark blue-gray and includes the text in white: “Conductors vs Insulators: Does It Matter?”
Play Video
Background image is a frame from the video showing insulator on one side and conductor on the other. In the foreground at the bottom are two boxes. The top is a bright blue with the StaticWorx logo. The second is a dark blue-gray and includes the text in white: “Conductors vs Insulators: Does It Matter?”
Play Video

Due to electrical safety risks and compliance with industry-specific grounding standards, conductive flooring is never recommended for schools, networked offices, E-9-1-1 call centers, flight towers or public-access environments. Conductive flooring is usually described as having an ohms resistance between 25,000 ohms and one million ohms. This is sometimes expressed in scientific notation as 2.5 X 10E4 – 1.0 X 10E6.

Static Dissipative refers to the ability of a material to dissipate static charges to ground at a controlled and safe rate. By definition, static dissipative flooring has an electrical resistance range, measured in ohms, of between 1,000,000 ohms and 1,000,000,000 ohms. 1.0 x 10 E6, (1 million ohms), to a maximum of 1.0 x 10 E9, (1 billion ohms).

Today, industry safety standards and most computer manuals recommend static-dissipative flooring – i.e. with resistance measuring below 1.0 x 10E6 – for end-user spaces such as critical call centers, PSAPs, flight towers, banks, government offices, and other facilities whose core mission relies on sophisticated or high-speed electronics.

Anti-Static refers to a material’s ability to suppress or prevent charge generation and static from building on people and equipment. Some materials marketed as antistatic are not capable of decaying a static charge fast enough to prevent unwanted ESD events from occurring. Antistatic – also known as computer grade or low kV – carpet, for example, is sprayed with a topical antistat that wears off over time. This type of carpet cannot be grounded. To eliminate static properly, anti-static carpet should be manufactured using yarns with carbon fibers. We call this type of carpet ESD carpet.

An Insulator is a material with an electrical resistance that prohibits a material from conducting a charge to ground. Examples of insulators are latex gloves, PVC shoe soles (on athletic shoes, for example), balloons, residential carpet, ceramic tile and VCT flooring. A practical example of an insulator is the extruded plastic casing around common electrical wires (which prevents electrocution by keeping electricity from leaking out of the wire), or a commercial carpet tile with a low 3.5 kV rating.

Background image shows a close up of an ohmmeter. The title ESD Flooring: Why Some Carpet Cannot Be Grounded is displayed in bold white text against a rectangle of dark blue grey at the bottom of the image and just above is the text "Static Shorts with StaticWorx - Right from the Den" and the StaticWorx logo
Play Video
Background image shows a close up of an ohmmeter. The title ESD Flooring: Why Some Carpet Cannot Be Grounded is displayed in bold white text against a rectangle of dark blue grey at the bottom of the image and just above is the text "Static Shorts with StaticWorx - Right from the Den" and the StaticWorx logo
Play Video
  • Why is static-dissipative carpet recommended over conductive carpet?

The lower the electrical resistance, the more rapidly a material can conduct an electrical charge. Because conductive materials offer a very low level of electrical resistance, they attract and decay electricity much more rapidly than static dissipative materials. A rapid decay of electricity can create a safety hazard if the grounded carpet is installed in spaces where people work near electrical appliances operating at 120, 220 and 440 volts. 

Research has shown that there is no performance advantage to an ESD carpet with high conductivity versus static-dissipative carpet. A risk-benefit analysis suggests that conductive carpet should not be installed in end-user spaces when there is a static-dissipative alternative available.

ShadowFX ESD Carpet tile is designed to be static dissipative. Static-dissipative carpet removes static charges at a measured rate, before charges can accumulate, keeping the environment safe from costly static interference. StaticWorx ShadowFX carpet prevents static interruptions in end-user spaces as well as in electronics manufacturing and handling environments (EPAs). 

Illustration demonstrating how ESD flooring works. The diagram shows cut off legs/foot standing on a conductive tile (labelled conductive tile with carbon pathways). A zoomed in cross-section is labelled "tile cross section: carbon veins". The next layer down is labelled "conductive adhesive". The next layer is labelled "concrete". From the conductive adhesive, copper stripping is shown with a grounding symbol and the label "connect to AC or bldg. ground". The diagram shows an electrical charge being carried from the person throw the conductive tile to the conductive adhesive and then along the copper stripping to ground.

How ShadowFX Carpet Works

ShadowFX ESD carpet contains electrically engineered static-dissipative fibers, which inhabit static from generating on carpet while simulatenously dissipating static charges safely to a ground source. These dissipative fibers link to a carbon pre-coat and our static dissipative backing. Static moves from there to an underlying conductive ground place to an earth ground.

24/7 Installation with no downtime

ShadowFX carpet tile can be installed with or without adhesives, making installation possible 24/7 without disruption or downtime. Our adhesive-free installation method (floating floor) is ideal for installation over raised access flooring panels.

Photograph of ShadowFX static-dissipative ESD carpet installed over raised access flooring. The floor uses PosiTile so tiles are easily removed to access the floor below as seen in the photo.
  • When should designers consider specifying StaticWorx static-dissipative carpet?

Whenever you select floor finishes for a facility that relies on the uninterrupted performance of computers or other sophisticated electronic equipment, you should consider using some form of static-preventive flooring. Most computer-reliant end-user environments require a floor that is capable of preventing static on people wearing ordinary everyday shoes (as opposed to special static-preventive footwear).

A diagram in three panels showing how walking body voltage works. The first panel shows someone walking across the floor and a build up of static. The text reads "1. Friction between the soles of shoes and the surface of the floor causes a transfer of electrons, leaving a positive charge on one surface and a negative charge on the other. This is called a triboelectric charge, or static electricity." The second panel shows a further build up of static electricity. The text reads: "As the person walks, static accumulates on the body. Humans can’t feel static until the charge reaches 3500 volts." The final panel shows someone at a desk touching electric equipment with a charge on their hand/arm. The text reads:" Static stays in place until the person touches someone or something, then the charge transfers, or discharges, to the other person or object. A static charge as low as 20 volts can damage or destroy sensitive electronic components."

This greatly limits the options, since most ESD flooring materials require the use of static-control shoes or ESD heel straps. Any type of static control vinyl, high pressure laminate and resinous flooring, for instance, will actually create static on people wearing standard footwear.

The only effective options for preventing static on ordinary footwear are either ESD rubber or ESD carpet tile. Carpet tiles are the quietest, most compatible (for sound attenuation and ergonomics) and least expensive form of ESD flooring for most environments. These factors make ShadowFX static-dissipative carpet an ideal option for networked offices, server rooms, control rooms, telecom rooms, switch and router facilities, 9-1-1 and standard call centers, flight towers and spaces using FAA flight equipment, data storage centers, financial areas, trading floors, NOCs, disaster recovery centers, media, communications, radar, medical monitoring, labs, tech spaces, networked classrooms as well as gaming and entertainment floors.

  • Which Industry Standards Does ShadowFX Carpet Meet?

StaticWorx warranties that ShadowFX ESD carpet tile, installed and maintained as recommended by StaticWorx, will not generate above .4kV volts of static electricity, measured according to AATCC #134. The carpet face will have a minimum resistance of 1.0 x 10E6 ohms and maximum resistance of 1.0 x 10E8 ohms, measured according to ANSI/ESD S7.1-2013. ShadowFX carpet tile will provide a system resistance that complies with ANSI/ESD S97.1 test limits for meeting ANSI/ESD S20.20 (< 1.0 x 10E9).

ShadowFX carpet tile meets the following standards for a grounded flooring installation:

ShadowFX ESD carpet tile is made in a sustainable factory using recycled materials.
100% carbon neutral over the life of the carpet.

Downloads

Partial image of Dave holding an ohmmeter. At the bottom, the series title Static Shorts with StaticWorx displays along with the logo in a blue box. Below that in a gray blue box is the episode title in white 'Low kV is Not Static Free'
Play Video
Image shows some of the steps of grounding as ESD floor as a background. The title How to Ground an ESD Floor is displayed in bold white text against a rectangle of dark blue grey at the bottom of the image and and the Staticworx logo below
Play Video
Background image shows a close up of an ohmmeter. The title ESD Flooring: Why Some Carpet Cannot Be Grounded is displayed in bold white text against a rectangle of dark blue grey at the bottom of the image and just above is the text "Static Shorts with StaticWorx - Right from the Den" and the StaticWorx logo
Play Video
Background image is an illustration of an ohmmeter and two probes. In the foreground at the bottom are two boxes. The top is a bright blue and includes the StaticWorx logo. The second is a dark blue-gray and includes the text in white: "Conductive Versus Dissipative: Does It Matter?"
Play Video

ShadowFX Static-dissipative (SC) Carpet Tile Collections

Carpet Tile for Access Flooring Applications

Looking for easy installation of Staticworx ESD Carpet Tile over your bare access floor panels?


ShadowFX SDC with TacTiles® is your solution.


  • Installation economy – no adhesive required
  • Guaranteed to meet all ESD standards for any application
  • ShadowFX carpet tiles with dissipative backing are grounded upon contact with metal panels Carpet tiles are easily lifted and replaced
ShadowFX Solids

With its simple, subtle texture and diversity of color options, Shadow FX SDC Solids is a popular choice for many styles of interior. It’s also ideal for mixing and matching with other Shadow FX SDC carpet tiles, to create accents, inserts, borders or checkerboard effects – a really useful, versatile tool for designers.


ShadowFX Patterns and Cubic Collections

After two or three years of use, carpet tiles exposed to chair casters and heavy traffic used to be prone to pile crush, making them look different from adjacent tiles. The main factor contributing to this problem was the pattern designs used in typical ESD carpet tile. All of these systems were either a solid pattern with slightly mottled colors or linear patterns with directional lines. Because carpet tiles appear seamless, like one large continuous floor, worn areas would stick out like a coffee stain on a white shirt.

 

The solution: Learning from nature.

 

Based on biomimicry – the study and imitation of nature’s best ideas to solve human problems – Staticworx ShadowFX static-dissipative (SD) carpet tiles mimic the organic design of nature. Tiles vary in patterns and colors within one style and colorway – all but eliminating the ability to observe pile crush or other forms of wear between tiles.

 

Because there’s no need to worry about matching dye lots, you need less attic stock and selective replacement is more effective. Replacement tiles are almost indistinguishable from older – original – tiles in the same installation.

 

Non-directional Installation for Less Installation Waste

 

ShadowFX SDC Patterns and Cubic Collections offer the added benefit of non-directional installation, meaning that tiles can be laid in any order or orientation. With no set pattern to maintain and no need to align tiles in a certain direction, there is significantly less installation waste. In fact, the average ShadowFX non-directional installation produces only 1.5% waste versus an average of 14% for other carpet styles. That means more of your floorcovering investment is on your floor, not in a dumpster.

 

And the best part, ShadowFX carpet tiles can be installed without glue, as a floating floor over any hard surface.

 

 
ShadowFX SDC Treez Budget-Friendly Collection

Simplicity Meets Style


Treez, our latest ShadowFX carpet tile collection, marries timeless style with the simplicity in nature. Tufted, textured loop construction adds dimension, creating a look as natural and stately as the bark on a tree. As appealing and comfortable in an uptown financial services space or high-tech lobby as in a workhorse application such as a data center or manufacturing facility.


ShadowFX SDC Parks Series

In sophisticated tones with threads of complementary colors in varying widths, our Parks Series carpet tile puts an earthy twist on classic linear design. A low-profile face uses less material for a tailored, upscale aesthetic.


ShadowFX SDC Peaks Collection

Like the stately summits of Vermont, our Peaks series carpet tile combines natural beauty with zen-like tranquility. Elegant in pattern and texture, with colorways in both warm and cool tones, our Peaks collection gives you a floor with dimension, functionality, and character.


ShadowFX SDC Fields & Stone Collection

Humans instinctively crave a connection to nature. Time spent in holistic places like Vermont provides a sense of comfort and wellbeing while promoting physical and mental health.


Inspired by the natural world, our ShadowFX Vermont Fields and Stone Carpet Tile Collection brings nature into the workspace, evoking feelings of serenity and refuge. A fusion of organic design and neutral color palette makes this dynamic collection as ideal for urban as for country or rural environments.


ShadowFX SDC Chenille Warp Carpet

ShadowFX SDC Chenille Warp Carpet is a tufted patterned level tip-sheared pile carpet tile, with SD backing. The pile material is made from recycled solution-dyed nylon. The fundamental aesthetic of Chenille is stripes which have been interpreted in a bold and textural way without relying on heavy face weight. Shadow FX Chenille Warp is available in colorways. The tiles can be installed in a variety of ways including quarter-turn, ashlar, brick fashion and parquet, with the potential to provide an unconventional appearance.


ShadowFX SDC Furrows II Carpet Tile

Linear precision, softened by texture and offset shapes.


As its name suggests, Furrows II has a resilient patterned loop pile carpet, reflecting the linear regularity of ploughed fields. Its textured, structured loop pile creates the three-dimensional impression of an aerial view of a cultivated landscape.


Designed for heavy contract performance, ShadowFX Furrows II maintains its distinctive appearance even in high-traffic areas. Pile yarn and backing contain pre-consumer recycled material, minimizing environmental impact.


Vermont Slate Carpet Tile

Built to withstand heavy traffic and abuse and designed to address the most stringent static control requirements – making Vermont Slate ideal for any application from electronics manufacturing to labs to 24/7 critical environments.


StaticWorx Vermont Slate carpet-tile collection provides the durability and high performance you expect from StaticWorx floors in a design that transports you to the mountains of Vermont. Warm, monochromatic earth tones promote a peaceful environment, inspiring creativity and a sense of wellbeing and connectedness.


The rock-like etchings in our Vermont Slate carpet tiles flow seamlessly across the surface of the floor in a non-directional or monolithic installation. Merge-ability enables mixing dye lots and saves money by allowing you to add new or replace worn or damaged tiles without worrying about dye lot compatibility.


  • Mergeable design – eliminates worry about matching dye lots
  • No fade – solution-dyed yarn prevents fading
  • Non-directional install method – easy to install and replace
  • Durable – rated for high traffic
  • Superior static control performance – meets the most stringent ESD standards including ANSI/ESD S20.20 and IEC 61340-5-1:2016*
    • Lifetime warranty for static control.
  • Static dissipative – meets standards for electronics manufacturing, telecom and government spaces**

Vermont Planx™

ShadowFX™ Planx offer a more expressive visual vocabulary.


Our 25cm x 1m Shadow FX ESD Planx bring new proportion and scale to carpet tile, giving you power to create fresh, exciting floor designs. The scale and directionality of Shadow FX ESD Planx creates floors that better reflect the geometry and flow of the surrounding space.


Planx or squares, our tiles all work together.


Use square tiles with contrasting Skinny Planks for large-scale tile patterns, provide wayfinding cues, or for work and activity zones. And this is just the beginning!


StaticWorx modular carpet tile and Planx work together in any combination, giving you a carpet tile design platform with unparalleled options.


A shape that’s better at hiding seams.


Want the benefits of carpet tile without the look of carpet tile? Use Shadow FX ESD Planx, same style and color, laid in an ashlar pattern. They’ll blend near seamlessly across the floor, giving you the benefits of modularity and the continuous look of broadloom.


A soft hard surface.


Love the look of wood plank flooring? Think luxury vinyl plank flooring is stunning? Patterns—like herringbone or ashlar—give ShadowFX Planx the visual appeal of other plank floors, with the patterning possibilities. You also get a floor covering that’s soft, quiet and much more economical than hard surfaces.


Get in Touch

The form below will help us better understand your needs and get you as quickly as possible to the right person. We look forward to helping you solve your static problem! 

You can expect a response within 24 hours. For faster service, please give us a call: 617-923-2000

Visit our privacy policy to find out how we process data.

Twitter
LinkedIn
Facebook
Reddit
Pinterest
Email
Background graphic is a still from the StaticWorx GroundSafe ESD Flooring – Your Trusted Partner explainer animation. In the foreground at the bottom are two boxes. The top is a bright blue with the StaticWorx logo and "GroundSafe ESD Flooring" underneath in white. The second is a dark blue-gray and includes the text in white: “GroundWorx ESD Flooring – Your Trusted Partner”
Play Video

StaticWorx high-performance static-control floors protect electronic components, explosives, and high-speed computers from damage caused by static electricity. ESD flooring is part of a system. Choices should always be based on objective, researched evidence. When you partner with us, we look at all possible items that may need to integrate with the floor, and, focusing on your goals and objectives, help you find the right floor for your application.

Get in Touch

East Coast: 617-923-2000
Email: [email protected]

“I’m so glad we were able to find an attractive solution that didn’t leave us with some run-of-the-mill ugly disaster.”

Unless otherwise stated, standards referenced are the most up-to-date versions.

Share This

subscribe to newsletter

Sign up for our newsletter and occasional updates.

The FAA has updated its standard for facilities and electronic equipment. StaticWorx meets all requirements for ESD flooring.

Flooring Products

Image shows the cards accepted for payment for StaticWorx: Visa, Mastercard, American Express and Discover

We accept these major credit cards.

“I’m so glad we were able to find an attractive solution that didn’t leave us with some run-of-the-mill ugly disaster.”

Share This

Get in Touch

East Coast: 617-923-2000
Email: [email protected]

subscribe to newsletter

Sign up for our newsletter and occasional updates.

The FAA has updated its standard for facilities and electronic equipment. StaticWorx meets all requirements for ESD flooring.

Unless otherwise stated, standards referenced are the most up-to-date versions.

Get in Touch

East Coast: 617-923-2000
Email: [email protected]

“I’m so glad we were able to find an attractive solution that didn’t leave us with some run-of-the-mill ugly disaster.”

Share This

subscribe to newsletter

Sign up for our newsletter and occasional updates.

The FAA has updated its standard for facilities and electronic equipment. StaticWorx meets all requirements for ESD flooring.

Unless otherwise stated, standards referenced are the most up-to-date versions.

This site is protected by copyright and trademark laws under both United States and International law.
All rights reserved. © 2008-2024, StaticWorx® GroundSafe® ESD Flooring. Privacy Policy